KRIWAN INT69 EXF2 Diagnose BASIC EX Protection Relay for Pumps in Ex Zones

Contact us for a price
Ask a question
KRIWAN-INT69EXF2-DIAG
Out of stock

KRIWAN INT69 EXF2 Diagnose BASIC EX protection relay

The INT69 EXF2 Diagnose BASIC EX is the version of the INT69 F Diagnose relay for pumps and agitators that operate in a potentially explosive atmosphere (Ex zone). The relay itself is mounted in the control cabinet, outside the Ex zone, and monitors the temperature sensors and leakage electrodes of the pump. Two relays switch the pump off safely when a limit value is exceeded.

A reset button and an external reset input are available after an interlocked shutdown. The run detection input records operating hours and switching cycles, so a service interval can also be monitored. Operating and fault data are stored in a non-volatile memory and can be read out with the KRIWAN INTspector app.

Main features

  • Temperature input 1: PTC (1–9 sensors in series)
  • Temperature input 2: bimetal contact
  • EMC-stable leakage monitoring by resistance measurement between electrodes
  • Run detection: operating hours, switching cycles, service interval
  • Non-volatile event memory, readable with the INTspector app
  • 2 relays: temperature and leakage
  • Reset button, external reset input and mains reset
  • Diagnostic port (DP) for the INTspector app and Modbus gateway
  • Tested to EN ISO 80079-37:2016, marking II (2) G [Ex h db] IIA

Versions

Article numberSupply voltage
20 A 713 P08124 V AC/DC, 50/60 Hz
22 A 713 P081100–240 V AC, 50/60 Hz

Technical data

Power consumption5 VA
Ambient temperature-20 … +60 °C
PTC measuring circuit1–9 PTC sensors in series (DIN VDE V 0898-1-401)
Bimetal circuitfor one NC contact, 24 V DC / 20 mA
Leakage measuring range10 kΩ … 1 MΩ
Run detection60–480 V AC phase-phase, 20–100 Hz, suitable for frequency converters
Relay contactsmax. 240 V AC / 2.5 A (C300), min. 24 V / 20 mA
Max. sensor cable length100 m (run detection: 3 m)
Degree of protectionIP20
ConnectionPush-in spring terminals, 0.2–2.5 mm²
Mounting35 mm DIN rail (EN 60715), 22.5 mm housing
Weightapprox. 200 g (24 V) / 250 g (100–240 V)
StandardsEN 61000-6-2, EN 61000-6-3, EN 61010-1, UL 60730, EN ISO 80079-37:2016

Typical applications: inlet pumping stations and wastewater pumps installed in Ex zones, explosion-protected agitators.

Technical data sheet / operating instructions (PDF, KRIWAN)

Contact us for technical advice and a quote.